The Containerized PV Substation is a fully integrated power conversion and distribution solution designed for utility-scale and commercial photovoltaic power plants. It combines the step-up transformer, medium-voltage switchgear, low-voltage switchgear, intelligent monitoring system, and auxiliary equipment in a standard containerized enclosure for fast deployment, simplified installation, and reliable long-term operation.
Engineered for efficiency, safety, and flexibility, the system steps up the low-voltage AC output from PV inverters to medium-voltage grid levels for efficient transmission and seamless grid connection.
The Containerized PV Substation is designed to step up inverter output voltage, typically 800 V AC, to medium-voltage levels such as 10 kV, 24 kV, or 35 kV.
Its integrated architecture helps reduce balance-of-system complexity while improving installation efficiency and overall system reliability.
With all major components assembled into a standard container platform, the unit offers a practical and scalable solution for modern solar power plants requiring rapid deployment, dependable performance, and simplified maintenance.
Fast Project DeliveryFactory-assembled, prewired, and pretested construction minimizes onsite installation work and shortens commissioning time.
High Energy YieldOptimized internal design reduces auxiliary power consumption and supports greater net energy delivery to the grid.
Reliable In Harsh EnvironmentsBuilt for demanding outdoor conditions, including high temperature, humidity, and dusty environments.
Compact And Highly IntegratedA space-saving containerized design combines multiple functional units in one complete substation solution.
Smart Monitoring And Easier O&MIntegrated monitoring and communication functions support real-time status visibility and remote operation.
| Parameter | Specification |
|---|---|
| Transformer Detection & Protection | Oil level, oil temperature, oil pressure |
| Protection Degree of MV & LV Room | IP54 |
| Internal Arcing Fault of STS | IAC A 20 kA 1s |
| MV Arc Releasing | Upward arc releasing for higher safety |
| MV Relay Protection | 50/51, 50N/51N |
| LV Overvoltage Protection | Type I + II |
| Anti-corrosion Protection | C5 |
| Parameter | 9000K | 6000K | 3000K |
|---|---|---|---|
| Dimensions (L × W × H) | 6,058 × 2,438 × 2,896 mm | 6,058 × 2,438 × 2,896 mm | 6,058 × 2,438 × 2,896 mm |
| Weight | < 28 t | < 23 t | <15 t |
| Operating Temperature Range | -25°C to +60°C | -25°C to +60°C | -25°C to +60°C |
| Relative Humidity | 0% to 95% non-condensing | 0% to 95% non-condensing | 0% to 95% non-condensing |
| Max. Operating Altitude | 1,000 m | 1,000 m | 1,000 m |
| MV-LV AC Connections | Prewired and pretested, no internal cabling onsite |
Prewired and pretested, no internal cabling onsite |
Prewired and pretested, no internal cabling onsite |
| LV & MV Room Cooling | Smart cooling without air-across for higher availability |
Smart cooling without air-across for higher availability |
Smart cooling without air-across for higher availability |
| Communication | Modbus TCP | Modbus TCP | Modbus TCP |
| Standards Compliance | IEC 62271-202 | IEC 62271-202 | IEC 62271-202 |
| Item | 9000K | 6000K | 3000K |
|---|---|---|---|
| Max. LV AC Inputs | 32 | 24 | 12 |
| AC Power | 9,000 kVA @ 40°C | 6,600 kVA @ 40°C | 3,000 kVA @ 40°C |
| Rated Input Voltage | 800 V | 800 V | 800 V |
| LV Panel Segregation | Form 2b | Form 2b | Form 2b |
| LV Main Switches | ACB (4,000 A, 2 × 1 pc) | ACB (2,900 A, 2 × 1 pc) | ACB (2,900 A, 1 × 1 pc) |
| LV Main Switches | MCCB (320 A, 2 × 16 pcs) | MCCB (320 A, 2 × 12 pcs) | MCCB (320 A, 12 pcs) |
| Item | Parameter |
|---|---|
| Rated Output Voltage | 10 kV to 35 kV |
| Frequency | 50 Hz or 60 Hz |
| Transformer Type | Oil-immersed, conservator type |
| Transformer Cooling Type | ONAN |
| Transformer Tappings | ±2 × 2.5% |
| Transformer Oil Type | Mineral oil, PCB-free |
| Transformer Vector Group | Dyn11-y11 |
| Transformer Minimum Peak Efficiency Index | Tier 1 or Tier 2 in accordance with EN 50588-1 |
| RMU Type | SF6 or SF6-free dry-air insulated |
| RMU Transformer Protection Unit | MV vacuum circuit breaker unit |
| RMU Cable Incoming / Outgoing Unit | Direct cable unit or cable load break switch unit |
| Auxiliary Transformer | Dry-type transformer, 15 kVA, single-phase, i0 |
| Auxiliary Transformer Output Voltage | 400 / 230 Vac |