Product Overview
The MNS2.0 low-voltage switchgear system is designed for indoor three-phase AC systems (50/60 Hz, 400 V) for electrical energy distribution and centralized motor control. It is applicable in power plants, industrial complexes, and commercial buildings.
● Compact, flexible design with arc-resistant materials for top safety.
CFC/halogen-free plastic components (flame-retardant, self-extinguishing).
Optimized internal layout boosts reliability, safety, and efficiency.
Arc Resistance and Structural SafetyFully type-tested for arc resistance, seismic stability & vibration resilience. Robust maintenance-free design ensures safety in harsh conditions, minimizing arc fault risks.
Reduced Downtime and Enhanced ReliabilityWithdrawable modules enable drawer replacement without power cut. Integrated intelligent control and protection units provide fault analysis, reducing production losses.
Predictive Maintenance and Remote MonitoringBuilt-in temperature monitoring enables predictive maintenance, real-time status visualization, and cloud analytics, boosting operational continuity and cutting maintenance costs.
| Basic Parameters | Parameter |
|---|---|
| Rated operational voltage | 400 V / 690 V (AC), 3P, 750 V (DC) |
| Rated insulation voltage | 690 V / 1000 V (AC), 3P, 1500 V (DC) |
| Rated impulse withstand voltage | 6 kV / 8 kV / 12 kV |
| Overvoltage category | Ⅱ/Ⅲ/Ⅳ |
| Rated frequency | Up to 60 Hz |
| Main busbar rated current | Up to 6300 A |
| Main busbar rated peak withstand current | Up to 220 kA |
| Main busbar rated short-time withstand current | Up to 100 kA |
| Seismic test | Intensity 9 |
| Internal arc | 85 kA/0.3s |
| Salt spray test | 168h salt spray test |
| EMC test | Class B |
Copyright © 2026 Henegia Electric All Rights Reserved