Product Overview
The KYN61-40.5 armored metal-enclosed switchgear is designed for 40.5kV single-busbar power systems, serving as a reliable solution for power reception, distribution, control, and protection.
● Robust switchgear with full internal arc resistance and AG3 (intensity 8) seismic rating. Features five-prevention interlocking, with an internal air clearance of ≥300mm, optimized cooling for ensuring safety. Compliant with major grid standards, authorized by national testing institutions.
Metal-Clad Safety DesignThe robust metal-clad enclosure prevents fault propagation and ensures operational safety.
High-Low Voltage IsolationComplete separation between high- and low-voltage compartments guarantees safety and system integrity.
Double-Sided Maintenance AccessCompact structure with dual-side maintenance design enhances accessibility and service efficiency.
Modular Circuit Breaker DesignSimplified and reliable modular breaker design ensures durability and extended operating life.
Five-Protection Interlocking SystemComprehensive interlocks prevent operational errors and support closed-door operation.
Arc Fault ResistanceDesigned to withstand internal arc faults up to 31.5kA/1s for enhanced protection.
Superior Insulation ClearanceMaintains insulation distances ≥300mm for safe and stable operation.
High-Altitude PerformanceOperates reliably at altitudes up to 3500m with composite insulation.
Certified ManufacturingFully compliant with Chinese and international standards, successfully passing all type tests.
Flexible Switch CompatibilitySupports vacuum circuit breakers and SF₆ circuit breakers for diverse applications.
Intelligent OperationEquipped with motorized breakers, grounding switches, and wireless temperature sensors for real-time monitoring and one-touch sequential control.
| Basic Parameters | |
|---|---|
| Insulation voltage | 40.5 kV |
| Rated insulation voltage | 40.5 kV |
| Rated power frequency withstand voltage | 95 kV/1min |
| Rated lightning impulse withstand voltage | 185 kV |
| Rated frequency | 50 Hz |
| Rated short-time withstand current (4s) | 40 kA |
| Rated peak withstand current | 100 kA |
| Rated busbar current | 4000 A |
| Rated branch busbar current | 4000 A |
| Internal arc fault withstand current | 31.5 kA/1s |
| IP rating | IP41 |
| IK rating | IK10 |
| Dimensions (width × depth × height, excluding front and rear doors) | 1400mm (1680mm) × 2750mm (2800mm/3050mm/3200mm) × 2600mm |
| Weight | 1000 kg - 2000 kg |