The HES Series Ring Main Unit (RMU) adopts a fully enclosed, gas-insulated design, with all live parts sealed inside a stainless-steel gas tank. This structure effectively isolates internal components from environmental influences, ensuring high reliability, enhanced safety, and maintenance-free operation.
The RMU supports top and side expansion and features a modular functional unit design, allowing flexible configuration to meet various project requirements. It can also be equipped with automation and intelligent monitoring solutions, delivering smart operation and value-added lifecycle services.
IEC 62271-100 Alternating-Current Circuit-Breakers
IEC 62271-102 Alternating-Current Disconnectors and Earthing Switches
IEC 62271-103 Switches for Rated Voltages above 1 kV and up to and including 52 kV
IEC 62271-200 A.C. Metal-Enclosed Switchgear and Controlgear for Rated Voltages above 1 kV and up to and including 52 kV
IEC 60529 Degrees of Protection Provided by Enclosures (IP Code)
IEC 62271-1 High-Voltage Switchgear and Controlgear - Part 1: Common Specifications
Proven Global PerformanceOver 20 years of experience, with installations in 65+ countries.
Standards ComplianceFully compliant with IEC, ANSI, and IEEE standards.
Strong Renewable Track RecordTotal installed capacity in renewables exceeds 70 GW.
Enhanced Safety DesignViewing windows enable visual verification of contact position, meeting IEEE requirements.
Intelligent O&MSmart components support condition monitoring and efficient operation.
High Manufacturing CapacityAnnual output exceeds 20,000 RMU units.
| Item | Unit | Vacuum CB Panel | Load Switch Panel |
|---|---|---|---|
| Rated Voltage | kV | 38 | |
| Rated Frequency | Hz | 50 / 60 | |
| Rated Power-Frequency Withstand Voltage (1min) | kV | 80 / 90 | |
| Rated Lightning Impulse Withstand Voltage | kV | 185 / 215 | |
| Rated Continuous Current | A | 630 | |
| Rated Short-Time Withstand Current (3s) | kA | 20 / 25 | |
| Rated Peak Withstand Current | kA | 52 / 65 | |
| Internal Arc Classification (IAC) | kA/s | 20/1, 25/1 | |
| Leakage Rates | V / V (% / year) | ≤ 0.01% | |
| Filling Level for Insulation and/or Switching Minimum Functional Gas Level for Insulation and/or Switching |
MPa (rel.) |
0.04 0.03 |
|
| Degree of Protection for Gas Tank | IP Code | IP67 | |
| Degree of Protection for Switchgear Enclosure (Indoor/Outdoor) | IP Code | IP4X / IP54 | |
| Rated Short-Circuit Breaking Current | kA | 20 / 25 | / |
| Mechanical Endurance | Times | 10000 | 5000 |
| Electrical Endurance | Grade | E2 | E2 |
| Dimension of Indoor Product in Inches (mm) | Width | 19.7 (500) | 17.7 (450) |
| Depth | 38.2 (970) | 38.2 (970) | |
| Height | 86.6 (2200) | 86.6 (2200) | |
Copyright © 2026 Henegia Electric All Rights Reserved